Skip to Main Content
Search distributed energy resources in New York

Chelsea Mercantile

Overview Chelsea Mercantile

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Oct 2013 to Dec 2018
2,418
MWh
electricity generated
Capacity
Factor
39,897
Mcf
generator fuel consumed
Electric
Efficiency
18,418
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Oct 2013 to Dec 2018
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 2,418 39,897 18,418 2,181 35.1 20.0 44.7 64.8
Oct 2013
21 362 219 9 19.1 19.5 58.7 78.1
Nov 2013
45 740 200 262 42.0 20.3 26.2 46.4
Dec 2013
52 844 293 160 46.5 20.4 33.6 54.0
Jan 2014
52 834 419 3 46.4 20.5 48.7 69.2
Feb 2014
65 1,025 505 2 64.0 20.8 47.7 68.6
Mar 2014
72 1,141 576 4 64.1 20.7 48.9 69.6
Apr 2014
70 1,110 526 51 64.5 20.7 45.9 66.6
May 2014
68 1,082 516 49 60.7 20.7 46.2 66.9
Jun 2014
86 1,371 561 130 80.0 20.8 39.7 60.5
Jul 2014
84 1,329 503 172 75.0 20.8 36.7 57.5
Aug 2014
81 1,284 516 145 72.4 20.8 39.0 59.8
Sep 2014
60 960 417 84 55.3 20.6 42.1 62.7
Oct 2014
73 1,167 548 58 65.6 20.7 45.5 66.2
Nov 2014
59 943 445 43 54.3 20.6 45.7 66.3
Dec 2014
60 960 430 65 53.5 20.6 43.4 63.9
Jan 2015
42 688 362 3 37.6 20.2 50.9 71.1
Feb 2015
44 716 402 2 43.3 20.2 54.5 74.7
Mar 2015
26 458 262 10 23.3 18.8 55.5 74.3
Apr 2015
14 279 109 52 13.3 17.0 37.9 54.9
May 2015
12 240 90 10 10.4 16.1 36.3 52.4
Jun 2015
20 365 0 9 18.3 17.9 0.0 17.9
Jul 2015
27 473 3 5 23.9 18.6 0.7 19.3
Aug 2015
23 409 212 5 20.4 18.4 50.2 68.7
Sep 2015
28 493 266 4 26.0 18.9 52.3 71.1
Oct 2015
30 526 284 4 27.0 19.0 52.4 71.4
Nov 2015
49 805 427 7 45.0 20.0 51.4 71.3
Dec 2015
29 504 281 9 25.7 18.8 54.1 73.0
Jan 2016
24 433 242 3 21.9 18.7 54.3 73.0
Feb 2016
28 481 263 3 26.8 19.2 52.9 72.1
Mar 2016
46 766 321 66 41.0 19.7 40.5 60.3
Apr 2016
58 951 434 55 53.3 20.0 44.2 64.3
May 2016
33 576 259 59 29.7 19.1 43.7 62.7
Jun 2016
11 220 121 4 10.4 16.8 53.1 69.9
Jul 2016
25 424 207 7 22.0 19.1 47.3 66.4
Aug 2016
29 485 250 8 25.6 19.5 49.9 69.4
Sep 2016
53 872 348 163 49.5 20.3 38.7 59.0
Oct 2016
51 838 364 125 46.0 20.2 42.1 62.3
Nov 2016
55 888 398 86 50.6 20.4 43.5 63.8
Dec 2016
64 1,040 508 55 57.6 20.4 47.3 67.8
Jan 2017
56 913 485 31 49.9 20.2 51.5 71.6
Feb 2017
41 675 317 26 40.8 20.1 45.4 65.6
Mar 2017
61 976 470 23 54.6 20.7 46.7 67.3
Apr 2017
35 569 260 11 32.2 20.2 44.3 64.5
May 2017
33 542 243 12 29.8 20.3 43.4 63.7
Jun 2017
0 0 0 0 0.0 0.0 0.0 0.0
Jul 2017
0 0 0 0 0.0 0.0 0.0 0.0
Aug 2017
0 0 0 0 0.0 0.0 0.0 0.0
Sep 2017
31 507 259 3 29.0 20.4 49.5 69.9
Oct 2017
33 542 274 4 29.2 19.9 48.9 68.8
Nov 2017
40 660 325 4 36.7 19.9 47.7 67.6
Dec 2017
30 504 248 4 26.8 19.6 47.7 67.3
Jan 2018
41 666 343 6 36.5 20.3 49.9 70.1
Feb 2018
26 440 217 5 26.1 19.8 47.7 67.5
Mar 2018
28 464 242 5 24.8 19.7 50.5 70.2
Apr 2018
20 345 196 6 18.7 19.3 54.9 74.2
May 2018
9 180 79 4 8.3 17.1 42.4 59.5
Jun 2018
6 127 59 2 5.6 15.7 45.0 60.7
Jul 2018
7 140 54 2 6.1 16.2 37.3 53.5
Aug 2018
21 351 161 10 18.5 19.4 44.3 63.7
Sep 2018
40 646 292 15 37.0 20.4 43.8 64.3
Oct 2018
34 550 267 9 30.3 20.3 47.0 67.3
Nov 2018
33 546 281 3 30.6 20.0 49.8 69.9
Dec 2018
29 471 261 3 30.6 20.1 53.8 73.9

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
Chelsea Mercantile 64.8 % 44.7 % 20.0 % 35.1 % 2,418 MWh
Top Peer 83.4 % 59.9 % 23.5 % 50.5 % 717 MWh
Average Peer 59.8 % 37.0 % 22.8 % 45.9 % 920 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Small (0-250 kW)
  • Facility Category: Residential
  • Total Peers in Group: 63

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Oct 2013 to Dec 2018
Peak Demand Reduction (kWP)
56
kW
Total Generation (kWhA)
2,418,188
kWh
Heat Recovered
18,418
MMBtu
Gas Consumed
39,897
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

76.0
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

72.0
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.