Performance Snapshot

Feb 2016 to Aug 2023
5,960
MWh
electricity generated
Capacity
Factor
82,923
Mcf
generator fuel consumed
Electric
Efficiency
28,269
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Feb 2016 to Aug 2023
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 5,960 82,923 28,269 2,803 28.0 23.8 33.0 56.8
Feb 2016
12 169 < 1 1 5.5 23.8 0.1 23.8
Mar 2016
64 762 444 < 1 26.7 27.6 56.5 84.1
Apr 2016
40 477 300 0 17.2 27.5 61.0 88.5
May 2016
90 1,083 716 < 1 38.0 27.6 64.0 91.6
Jun 2016
36 450 329 0 15.7 26.6 70.8 97.5
Jul 2016
61 740 482 < 1 25.5 27.1 63.1 90.1
Aug 2016
21 262 179 0 9.0 27.0 66.2 93.2
Sep 2016
70 852 580 0 30.5 27.3 66.0 93.3
Oct 2016
91 1,134 684 0 38.3 26.6 58.4 85.0
Nov 2016
157 1,976 1,069 16 68.0 26.2 52.5 78.7
Dec 2016
71 888 477 < 1 29.7 26.3 52.1 78.4
Jan 2017
0 0 0 0 0.0 0.0 0.0 0.0
Feb 2017
147 1,851 984 10 68.3 26.2 51.5 77.8
Mar 2017
144 1,835 774 250 60.4 25.9 40.9 66.8
Apr 2017
105 1,357 701 84 45.7 25.7 50.1 75.8
May 2017
104 1,337 635 196 43.6 25.7 46.0 71.7
Jun 2017
42 533 225 106 18.2 25.9 40.8 66.8
Jul 2017
0 0 0 0 0.0 0.0 0.0 0.0
Aug 2017
0 0 0 0 0.0 0.0 0.0 0.0
Sep 2017
0 0 0 0 0.0 0.0 0.0 0.0
Oct 2017
0 0 0 0 0.0 0.0 0.0 0.0
Nov 2017
0 0 0 0 0.0 0.0 0.0 0.0
Dec 2017
0 0 0 0 0.0 0.0 0.0 0.0
Jan 2018
0 0 0 0 0.0 0.0 0.0 0.0
Feb 2018
0 0 0 0 0.0 0.0 0.0 0.0
Mar 2018
0 0 0 0 0.0 0.0 0.0 0.0
Apr 2018
116 1,612 461 10 50.3 23.8 27.7 51.5
May 2018
83 1,109 493 15 34.7 24.6 43.1 67.7
Jun 2018
82 1,109 476 25 35.7 24.5 41.6 66.1
Jul 2018
75 1,040 448 27 31.7 24.0 41.7 65.7
Aug 2018
80 1,149 444 48 33.4 22.9 37.4 60.3
Sep 2018
92 1,319 465 104 39.7 22.9 34.2 57.1
Oct 2018
129 1,830 661 179 54.2 23.3 35.0 58.3
Nov 2018
123 1,734 457 234 53.2 23.4 25.5 48.9
Dec 2018
144 2,012 697 221 60.6 23.7 33.6 57.3
Jan 2019
155 2,113 624 317 65.2 24.3 28.6 52.9
Feb 2019
124 1,696 694 8 57.8 24.3 39.6 63.9
Mar 2019
128 1,927 715 0 53.8 22.0 36.0 57.9
Apr 2019
80 1,247 442 8 34.8 21.3 34.3 55.6
May 2019
52 894 311 0 21.9 19.3 33.7 53.0
Jun 2019
65 1,098 372 7 28.2 19.6 32.8 52.4
Jul 2019
74 1,149 343 3 30.9 21.2 28.9 50.1
Aug 2019
48 744 268 5 20.2 21.3 34.9 56.3
Sep 2019
57 847 298 4 24.6 22.1 34.1 56.3
Oct 2019
84 1,326 446 1 35.3 21.0 32.6 53.6
Nov 2019
82 1,228 269 2 35.7 22.2 21.2 43.4
Dec 2019
71 989 230 4 29.7 23.6 22.5 46.2
Jan 2020
0 0 0 0 0.0 0.0 0.0 0.0
Feb 2020
24 318 141 < 1 10.7 24.9 43.0 67.9
Mar 2020
135 1,836 929 < 1 56.9 24.4 49.0 73.4
Apr 2020
100 1,375 582 < 1 43.4 24.1 41.0 65.1
May 2020
67 964 468 < 1 28.2 23.1 47.1 70.2
Jun 2020
67 973 449 4 29.2 22.8 44.7 67.5
Jul 2020
69 1,003 450 7 29.1 22.8 43.5 66.3
Aug 2020
92 1,292 451 34 38.6 23.5 33.8 57.3
Sep 2020
122 1,699 496 111 53.0 23.8 28.3 52.1
Oct 2020
88 1,261 581 14 37.1 23.2 44.6 67.8
Nov 2020
126 1,751 832 19 54.8 23.9 46.0 69.9
Dec 2020
137 1,870 800 51 57.7 24.3 41.5 65.8
Jan 2021
138 1,865 782 47 58.0 24.5 40.6 65.1
Feb 2021
104 1,418 589 34 48.2 24.2 40.2 64.4
Mar 2021
135 1,860 848 29 56.6 24.0 44.2 68.1
Apr 2021
123 1,754 821 19 53.4 23.2 45.4 68.6
May 2021
101 1,469 648 24 42.3 22.7 42.7 65.4
Jun 2021
67 975 206 3 29.2 22.8 20.5 43.3
Jul 2021
69 1,003 < 1 3 29.2 22.9 0.0 22.9
Aug 2021
69 1,007 < 1 3 29.1 22.8 0.0 22.8
Sep 2021
67 986 0 0 29.3 22.6 0.0 22.6
Oct 2021
< 1 10 0 0 0.3 22.4 0.0 22.4
Nov 2021
< 1 1 0 0 < 0.1 3.3 0.0 3.3
Dec 2021
0 0 0 0 0.0 0.0 0.0 0.0
Jan 2022
0 0 0 0 0.0 0.0 0.0 0.0
Feb 2022
0 0 0 0 0.0 0.0 0.0 0.0
Mar 2022
0 0 0 0 0.0 0.0 0.0 0.0
Apr 2022
0 0 0 0 0.0 0.0 0.0 0.0
May 2022
0 0 0 0 0.0 0.0 0.0 0.0
Jun 2022
0 0 0 0 0.0 0.0 0.0 0.0
Jul 2022
0 0 0 0 0.0 0.0 0.0 0.0
Aug 2022
72 935 < 1 134 30.0 25.3 0.0 25.3
Sep 2022
16 208 < 1 28 6.9 25.4 0.0 25.4
Oct 2022
0 0 0 0 0.0 0.0 0.0 0.0
Nov 2022
83 1,172 0 165 35.9 23.3 0.0 23.3
Dec 2022
72 1,046 < 1 161 30.2 22.7 0.0 22.7
Jan 2023
56 782 < 1 10 23.5 23.7 0.1 23.7
Feb 2023
101 1,428 1 2 46.9 23.4 0.1 23.4
Mar 2023
70 975 < 1 1 29.4 23.7 0.0 23.7
Apr 2023
99 1,427 < 1 < 1 43.2 23.0 0.0 23.1
May 2023
119 1,739 < 1 2 49.8 22.6 0.0 22.6
Jun 2023
78 1,200 < 1 4 33.8 21.5 0.0 21.5
Jul 2023
2 35 0 < 1 1.0 21.9 0.0 21.9
Aug 2023
92 1,409 < 1 1 41.1 21.5 0.0 21.5

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
AVA High Line 56.8 % 33.0 % 23.8 % 28.0 % 5,960 MWh
Top Peer 73.0 % 46.6 % 26.5 % 52.6 % 7,079 MWh
Average Peer 51.8 % 26.8 % 25.0 % 31.4 % 2,930 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Medium (250-1000 kW)
  • Facility Category: Residential
  • Total Peers in Group: 31

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Feb 2016 to Aug 2023
Peak Demand Reduction (kWP)
122
kW
Total Generation (kWhA)
5,959,968
kWh
Heat Recovered
28,269
MMBtu
Gas Consumed
82,923
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

65.1
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

63.1
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.