Skip to Main Content
Search distributed energy resources in New York

SUNY ESF

Overview SUNY ESF - Microturbine SUNY ESF - Steam Turbine

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Jul 2016 to Aug 2023
3,658
MWh
electricity generated
Capacity
Factor
66,941
Mcf
generator fuel consumed
Electric
Efficiency
18,711
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Jul 2016 to Aug 2023
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 3,658 66,941 18,711 0 30.1 18.1 27.1 45.2
Jul 2016
0 12 < 1 0 0.0 0.0 0.5 0.5
Aug 2016
11 261 64 0 7.4 13.5 23.8 37.3
Sep 2016
46 1,058 273 0 32.7 14.4 25.0 39.3
Oct 2016
41 902 240 0 28.2 15.0 25.7 40.7
Nov 2016
81 1,545 434 0 57.9 17.4 27.2 44.6
Dec 2016
104 1,840 511 0 71.9 18.7 26.9 45.7
Jan 2017
99 1,726 420 0 68.1 18.9 23.6 42.5
Feb 2017
83 1,488 356 0 63.7 18.5 23.2 41.7
Mar 2017
36 601 164 0 24.6 19.6 26.5 46.1
Apr 2017
25 474 132 0 17.6 17.2 26.9 44.1
May 2017
54 1,036 295 0 37.3 17.3 27.6 44.8
Jun 2017
29 588 155 0 20.6 16.3 25.6 41.9
Jul 2017
60 1,231 314 0 41.6 16.2 24.7 40.9
Aug 2017
36 756 220 0 24.6 15.6 28.2 43.9
Sep 2017
47 967 278 0 33.4 16.0 27.9 43.9
Oct 2017
62 1,211 351 0 42.5 16.8 28.1 45.0
Nov 2017
81 1,444 417 0 57.6 18.5 28.0 46.5
Dec 2017
49 857 227 0 33.6 18.8 25.7 44.5
Jan 2018
90 1,557 322 0 61.7 19.0 20.0 39.0
Feb 2018
64 1,223 393 0 49.0 17.4 31.1 48.5
Mar 2018
78 1,548 476 0 54.0 16.7 29.8 46.5
Apr 2018
55 1,143 366 0 39.1 15.9 31.0 46.9
May 2018
39 960 296 0 27.1 13.6 29.9 43.5
Jun 2018
11 282 84 0 8.1 13.3 28.9 42.2
Jul 2018
5 151 44 0 3.5 11.2 28.3 39.4
Aug 2018
0 0 0 0 0.0 0.0 0.0 0.0
Sep 2018
0 0 0 0 0.0 0.0 0.0 0.0
Oct 2018
0 0 0 0 0.0 0.0 0.0 0.0
Nov 2018
66 1,170 350 0 47.0 18.7 29.0 47.7
Dec 2018
54 987 296 0 37.1 18.0 29.1 47.1
Jan 2019
89 1,571 478 0 61.4 18.7 29.5 48.2
Feb 2019
89 1,577 479 0 68.3 18.8 29.4 48.2
Mar 2019
94 1,706 519 0 64.7 18.2 29.5 47.7
Apr 2019
28 517 160 0 19.9 17.9 29.9 47.8
May 2019
0 0 0 0 0.0 0.0 0.0 0.0
Jun 2019
0 0 0 0 0.0 0.0 0.0 0.0
Jul 2019
33 666 192 0 22.5 16.2 27.9 44.2
Aug 2019
31 624 172 0 21.6 16.6 26.7 43.3
Sep 2019
31 466 128 0 22.0 21.9 26.5 48.4
Oct 2019
88 896 259 0 60.8 32.5 28.0 60.6
Nov 2019
15 265 79 0 11.0 19.3 28.9 48.2
Dec 2019
83 1,367 401 0 56.9 20.0 28.4 48.4
Jan 2020
88 1,445 428 0 61.0 20.2 28.7 49.0
Feb 2020
79 1,293 388 0 58.4 20.3 29.1 49.4
Mar 2020
85 1,431 422 0 58.8 19.7 28.5 48.3
Apr 2020
84 1,442 421 0 59.8 19.2 28.3 47.5
May 2020
59 1,074 296 0 40.8 18.2 26.7 44.9
Jun 2020
25 535 151 0 17.6 15.3 27.3 42.6
Jul 2020
28 640 178 0 19.3 14.5 26.9 41.4
Aug 2020
32 676 180 0 21.8 15.5 25.8 41.3
Sep 2020
14 309 89 0 10.1 15.2 28.0 43.2
Oct 2020
66 1,242 363 0 45.7 17.7 28.3 46.0
Nov 2020
42 762 224 0 30.2 18.4 28.5 46.9
Dec 2020
88 1,502 456 0 60.6 19.4 29.4 48.8
Jan 2021
88 1,502 457 0 60.8 19.4 29.5 48.9
Feb 2021
96 1,564 475 0 73.4 20.3 29.4 49.7
Mar 2021
88 1,611 469 0 60.9 18.1 28.2 46.4
Apr 2021
56 1,005 297 0 39.9 18.4 28.6 47.1
May 2021
62 1,171 308 0 42.6 17.4 25.5 42.9
Jun 2021
44 934 210 0 31.5 15.7 21.8 37.4
Jul 2021
4 82 22 0 2.7 15.8 25.6 41.4
Aug 2021
17 411 96 0 11.9 13.9 22.7 36.6
Sep 2021
35 741 192 0 25.1 15.7 25.2 40.9
Oct 2021
62 1,199 289 0 42.5 17.0 23.3 40.4
Nov 2021
78 1,391 372 0 55.7 18.6 25.9 44.5
Dec 2021
89 1,564 410 0 61.1 18.7 25.4 44.1
Jan 2022
33 606 170 0 23.1 18.3 27.2 45.5
Feb 2022
0 2 < 1 0 0.0 0.0 0.4 0.4
Mar 2022
11 207 58 0 7.5 17.5 27.4 44.9
Apr 2022
52 955 251 0 37.0 18.0 25.4 43.4
May 2022
53 864 208 0 36.5 20.3 23.3 43.5
Jun 2022
36 527 120 0 25.6 22.5 22.0 44.6
Jul 2022
27 589 108 0 18.3 14.9 17.8 32.7
Aug 2022
4 134 18 0 3.0 10.8 12.7 23.5
Sep 2022
13 276 73 0 9.2 15.5 25.7 41.2
Oct 2022
31 580 166 0 21.6 17.8 27.8 45.6
Nov 2022
0 0 0 0 0.0 0.0 0.0 0.0
Dec 2022
0 0 0 0 0.0 0.0 0.0 0.0
Jan 2023
0 0 0 0 0.0 0.0 0.0 0.0
Feb 2023
0 0 0 0 0.0 0.0 0.0 0.0
Mar 2023
0 0 0 0 0.0 0.0 0.0 0.0
Apr 2023
0 0 0 0 0.0 0.0 0.0 0.0
May 2023
0 0 0 0 0.0 0.0 0.0 0.0
Jun 2023
0 0 0 0 0.0 0.0 0.0 0.0
Jul 2023
0 0 0 0 0.0 0.0 0.0 0.0
Aug 2023
0 0 0 0 0.0 0.0 0.0 0.0

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
SUNY ESF 45.2 % 27.1 % 18.1 % 30.1 % 3,658 MWh
Top Peer 52.1 % 27.3 % 24.7 % 46.0 % 881 MWh
Average Peer 45.1 % 23.5 % 21.6 % 29.8 % 1,585 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Small (0-250 kW)
  • Facility Category: Education
  • Total Peers in Group: 4

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Jul 2016 to Aug 2023
Peak Demand Reduction (kWP)
90
kW
Total Generation (kWhA)
3,658,317
kWh
Heat Recovered
18,711
MMBtu
Gas Consumed
66,941
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

51.9
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

50.2
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.