Skip to Main Content
Search distributed energy resources in New York

The St Tropez

Overview St. Tropez Condominium

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Jul 2016 to Jul 2020
2,811
MWh
electricity generated
Capacity
Factor
35,357
Mcf
generator fuel consumed
Electric
Efficiency
12,117
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Jul 2016 to Jul 2020
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 2,811 35,357 12,117 0 39.7 26.3 33.2 59.5
Jul 2016
62 788 0 0 41.7 26.1 0.0 26.1
Aug 2016
103 1,301 0 0 69.5 26.3 0.0 26.3
Sep 2016
129 1,598 0 0 89.6 26.7 0.0 26.7
Oct 2016
74 939 0 0 50.0 26.2 0.0 26.2
Nov 2016
101 1,263 0 0 70.4 26.5 0.0 26.5
Dec 2016
135 1,645 0 0 90.5 27.1 0.0 27.1
Jan 2017
127 1,574 0 0 85.1 26.6 0.0 26.6
Feb 2017
108 1,338 0 0 80.5 26.8 0.0 26.8
Mar 2017
117 1,443 0 0 78.7 26.8 0.0 26.8
Apr 2017
54 690 0 0 37.8 26.1 0.0 26.1
May 2017
30 388 0 0 20.2 25.6 0.0 25.6
Jun 2017
97 1,227 592 0 67.1 26.0 46.7 72.8
Jul 2017
93 1,181 615 0 62.3 25.9 50.4 76.4
Aug 2017
125 1,555 850 0 84.1 26.6 52.9 79.6
Sep 2017
61 760 437 0 42.4 26.6 55.7 82.3
Oct 2017
25 319 172 0 17.0 26.2 52.2 78.4
Nov 2017
69 871 474 0 48.1 26.3 52.8 79.0
Dec 2017
81 993 542 0 54.3 26.9 52.9 79.8
Jan 2018
81 986 532 0 54.2 27.1 52.2 79.3
Feb 2018
104 1,260 671 0 77.3 27.3 51.6 78.9
Mar 2018
137 1,689 887 0 92.4 26.9 50.9 77.8
Apr 2018
46 560 292 0 32.2 27.3 50.5 77.9
May 2018
50 626 370 0 33.8 26.6 57.2 83.8
Jun 2018
49 624 346 0 34.0 25.9 53.8 79.7
Jul 2018
78 986 500 0 52.7 26.3 49.1 75.4
Aug 2018
84 1,063 482 0 56.2 26.0 43.9 70.0
Sep 2018
0 0 0 0 0.0 0.0 0.0 0.0
Oct 2018
37 475 247 0 24.8 25.7 50.4 76.1
Nov 2018
64 803 415 0 44.2 26.2 50.0 76.3
Dec 2018
27 345 180 0 18.4 26.2 50.6 76.8
Jan 2019
17 225 115 0 11.7 25.6 49.5 75.0
Feb 2019
16 209 105 0 12.1 25.8 48.9 74.7
Mar 2019
72 906 467 0 48.1 26.1 50.0 76.1
Apr 2019
14 176 91 0 9.4 25.4 49.9 75.3
May 2019
61 804 466 0 41.3 25.3 56.2 81.5
Jun 2019
65 861 527 0 45.1 25.0 59.3 84.3
Jul 2019
95 1,258 786 0 63.7 24.9 60.5 85.5
Aug 2019
76 1,018 635 0 51.0 24.6 60.4 85.1
Sep 2019
0 0 0 0 0.0 0.0 0.0 0.0
Oct 2019
0 0 0 0 0.0 0.0 0.0 0.0
Nov 2019
0 0 0 0 0.0 0.0 0.0 0.0
Dec 2019
0 0 0 0 0.0 0.0 0.0 0.0
Jan 2020
0 0 0 0 0.0 0.0 0.0 0.0
Feb 2020
0 0 0 0 0.0 0.0 0.0 0.0
Mar 2020
3 38 19 0 1.8 23.8 49.3 73.1
Apr 2020
0 0 0 0 0.0 0.0 0.0 0.0
May 2020
< 1 12 3 0 0.6 25.5 23.2 48.7
Jun 2020
35 477 262 0 24.4 24.4 53.2 77.6
Jul 2020
6 83 37 0 10.1 25.2 43.2 68.4

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
The St Tropez 59.5 % 33.2 % 26.3 % 39.7 % 2,811 MWh
Top Peer 82.6 % 57.0 % 25.6 % 76.7 % 486 MWh
Average Peer 60.6 % 37.2 % 23.4 % 42.6 % 991 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Small (0-250 kW)
  • Facility Category: Residential
  • Total Peers in Group: 85

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Jul 2016 to Jul 2020
Peak Demand Reduction (kWP)
109
kW
Total Generation (kWhA)
2,810,975
kWh
Heat Recovered
12,117
MMBtu
Gas Consumed
35,357
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

67.8
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

66.1
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.